Wilo-EMUport FTS MG - solids separation system
| Type key Example: |
Wilo-EMUport FTS MG 750-1500 |
| FTS |
Solids separation system |
| M |
Version
(M = compact version, F = large version) |
| S |
Type of installation
(G = in building, S = with PE-HD sump) |
| 750 |
Installation depth below inlet floor in mm |
| 1500 |
Sump diameter in mm |
|
|
Wilo-EMUport FTS MG - solids separation system
Design
Sewage lifting unit with compact solids separation system for installation in a building or concrete sump
Applications
• System for installation in an existing structure (building or concrete sump).
• Sewage lifting unit with compact solids separation system for drainage of commercial buildings and complexes (e.g. hotels, department stores, etc.), small residential estates or as a replacement system for the refurbishment of existing large concrete sumps.
Special features/product advantages
• Energy saving due to pumps with narrow ball passage, which produces better efficiency than with conventional sewage pumping stations
• Considerably less susceptible to plugging as the pumps do not come into contact with the solids in the wastewater
• Uninterrupted operation during maintenance or repair work due to the station's double-pump design and individual shut-off of the solids separation reservoirs
• All parts are accessible from outside, so very easy to maintain and hygienic
• Resistance to corrosion and long life due to construction from PE-HD material
Technical data
• Max. inlet: 45 m3/h
• Max. useable tank volume: 500 l
• Max. delivery head: 65 m
• Suction head: 400 - 1200 mm
• Mains connection: 3~400 V, 50 Hz
Equipment/function
• Solids separation system with solids separation reservoir and collectio reservoir
• Two dry-well installed submersible sewage pumps for alternating mode
• Switching system and level measurement according to customer request
• Individual shut-off of the solids collection reservoirs
Materials
• Solids separation system: PE-HD
• Pipework: PE-HD
• Pumps and non-return ball valves: grey cast iron, coated
Description/design
Connection-ready fully submersible sewage pumping station with solids separation system and a gas- and watertight collection tank. Equipped as a double-pump system with submersible sewage pumps, running in alternating mode. Easy handling and optimum tank drainage by means of depth suction. Due to the use of solids separation tanks, the pumps do not come into contact with the solids in the fluid. In this way, pumps with narrow ball passages and optimised efficiency can be used for pumping sewage. The dry well installation of the pumps and their configuration as a redundant double-pump system ensures maximum hygiene, ease of maintenance, and operational reliability. The complete system, apart from the pumps and non-return valve, is made of corrosion-resistant PE-HD..
Attention:
The accompanying switchgear is not submersible and must for that reason be arranged in such a way that it is secure against flooding.
Options
• Other reservoir sizes and suction heads can be produced as requested by the customer, e.g. due to existing installation openings or door dimensions.
• Inductive flow rate gauge
• Slide valve for inlet
• Slide valve for discharge pipeline
• Flange outlet for discharge pipeline
• Flush connection
Scope of delivery
• Ready-to-install solids separation system
• Two sewage pumps with 10 m cable
• Individual shut-off of the solids separation reservoirs
• Switchgear with level measurement
• Discharge pipe junction with smooth pipe end
• Non-return valve
Dimensioning
The installation must be configured for the maximum wastewater flow occurring, including a possible additional peak flow. The pumps must be configured for a minimum flow velocity of 0.7 m/s in the discharge pipeline (e.g. min. 21.6 m³/h with DN 100 pipe). The manometric delivery head is calculated as the maximum static head + pipeline friction losses + pumping station losses of 1.0 mWS.
Downloads
Wilo-EMU Port Product Information
|